2026-11-28
Project Background & Challenge
Manufacturing precision Automatic Self Cleaning Filter and Hydraulic Filter assemblies, LEFILTER supported a Tier-IV banking data center in São Paulo, Brazil, in upgrading its 30% propylene-glycol chilled water loop. Because glycol solutions tend to loosen historical rust and gasket residue inside older piping networks, suspended particulates were prematurely wearing out mechanical pump seals and fouling precision CRAH coils.
Solution: Closed-Loop Brush-Type Automatic Self Cleaning FilterBecause glycol fluid is expensive and cannot be wasted during drain cycles, LEFILTER customized a low-purge Automatic Self Cleaning Filter equipped with a 75-micron 316L wedge-wire screen and an integrated sludge collection chamber. The Automatic Self Cleaning Filter brushes debris into a concentrated sump and opens the drain valve for only 3 seconds per cycle, recovering over 99.6% of the glycol coolant.
Technical Parameters
Application: Tier-IV Data Center 30% Propylene-Glycol Chilled Loop
Equipment: Low-Loss Brush Automatic Self Cleaning Filter (DN150)
Filtration Precision: 75 Micron
Flow Capacity: 180 m³/h
Seals & Elastomers: Viton (FKM) Glycol-Compatible Seals
Coolant Recovery Rate: > 99.6%
Results & Customer ValueGlycol loss during automated cleaning was reduced to negligible levels, pump mechanical seal failures ceased completely, and system cleanliness met strict OEM chiller warranty standards.