Project Background & ChallengeProviding industrial-grade Self Cleaning Filter and Air compressor filter equipment worldwide, LEFILTER resolved a severe condenser fouling issue for an enterprise financial data center in Navi Mumbai, India. Surrounded by active urban construction and monsoon winds, the rooftop evaporative cooling towers ingested heavy loads of airborne silica dust, soot, and organic matter, causing conventional basket strainers to clog every 48 hours.
Solution: Heavy-Duty Scraper Self Cleaning FilterTo handle high suspended solids without screen blinding, LEFILTER installed two DN200 motorized scraper Self Cleaning Filter systems in a side-stream basin-sweeping loop. Driven by a heavy-duty helical gear motor, an internal spring-loaded PTFE/316L scraper blade continuously shears sticky silt and biofilm off the 120-micron wedge-wire cylinder, discharging concentrated sludge through an automated pneumatic ball valve.
Technical Parameters
Application: Data Center Condenser Basin Sweeping & Side-Stream Filtration
Equipment: Scraper-Type Self Cleaning Filter (DN200)
Filtration Rating: 120 Micron
Design Flow Rate: 280 m³/h
Housing Material: Carbon Steel with Epoxy Anti-Corrosion Coating (Screen: SS316L)
Flush Water Loss: < 0.8% of total treated flow
Results & Customer ValueManual strainer cleaning labor was completely eliminated, chiller condenser approach temperature dropped by 2.1°C, and annual water makeup savings exceeded 12,000 cubic meters.