2026-11-28
Project Background & ChallengeAs a specialized manufacturer of Self Cleaning Filter and Liquid Filters, LEFILTER engineered a corrosion-resistant pre-filtration package for a coastal colocation data center in Jurong, Singapore. Because freshwater resources are strictly rationed, the facility draws treated seawater and reclaimed NEWater for its heat rejection loop. Marine microorganisms, fine silt, and suspended algae frequently fouled downstream titanium plate heat exchangers, threatening cooling stability during peak tropical temperatures.
Solution: Super Duplex Backwash Self Cleaning FilterTo withstand high chloride levels without pitting corrosion, LEFILTER fabricated three DN300 suction-scanner Self Cleaning Filter units constructed from Super Duplex 2507 stainless steel. Installed directly ahead of the titanium plate heat exchangers, each Self Cleaning Filter uses an 80-micron sintered wedge-wire screen and an automated differential pressure flushing cycle (triggered at 0.04 MPa) to purge marine debris without interrupting continuous 24/7 water flow.
Technical Parameters
Application: Coastal Data Center Seawater Heat Exchanger Protection
Equipment Model: Suction-Scanner Self Cleaning Filter (DN300)
Filtration Rating: 80 Micron
Design Flow Rate: 600 m³/h per unit
Wetted Material: Super Duplex SS2507
Control Mode: Differential Pressure & Timer Automated PLC
Results & Customer ValueHeat exchanger differential pressure remained stable across twelve months of continuous operation, eliminating bi-weekly manual dismantling and cutting chemical biocides consumption by 30%.